ACI 318 / ACI 133 - Coupler Codes and Standard in Building code Requirements for Structural Concrete and Commentary
American Concrete Institute (ACI) Building Code 318 -
- Building code Requirements for Structural Concrete and Commentary
ACI 318 /
ACI 133
ACI 318 / ACI 133 |
||
Type of Test Required |
Why ! (purpose of the test) |
What is the Criteria ? |
Static
tensile strength test |
Tensile strength of the Rebar joint (Rebar to Coupler Splice) joint |
> 1.25fy for Type 1 100% fu & >1.25fy for Type 2 Fu = Ultimate Strength of bar Fy = Yield Strength of bar |
Slip Test |
Used to make sure that the plastic movement
(slip) between the reinforcement bars with in the Mechanical Splice, when Loaded
in tension |
The bar-splice assembly shall be loaded in
tension to nominal zero load, not exceeding 4Mpa (600 psi). The bar-splice assembly then be loaded in tension
with a loading rate between 70 Mpa/min to 690 Mpa/min. |
Montonic Tensile test for
failure |
Used to measure the performance of a mechanical splice
under an increasing tensile load. The load is increased until failure is reached. |
Monotonic Tension Tests shall be conducted in
accordance with the provisions of Test Methods ASTM A370. Up to the yield point, Load shall be applied at
the rate between 70 Mpa/min (10,000 psi) and 700 Mpa (100,000 psi) |
Monotonic Compression Test |
This test is
used to ascertain the performance of the bar-splice assembly under an
increasing compressive load. |
Monotonic Compression Tests shall be conducted in
accordance with the provision of Test Methods ASTM A370 and E9. For strain rate controlled tests, the load shall
be applied in accordance with 8.7 of Test Methods ASTM E9. Typical maximum compressive load imposed in this
test is 125% of the specified yield strength of the reinforcement bar. |
Uniform Cyclic Load Test (Seismic Elastic) Stage 1 |
Used to make sure how a mechanical splice performs
when subjected to alternating tension and compression loads for
a given number of cycles. Each cycle may exceed the specified yield strain of
the reinforcement bar and is intended to stimulate an earthquake loading. |
The test specimen shall be loaded between 70 Mpa/min
to 690 Mpa/min until the strain specified has been reached. The loading direction shall be reversed until the
specimen has reached the compressive loads specified. 20 Cycles of stress variation from 50%
compressive – 95% tensile of fy |
Stepped Strain Cyclic
Load Test (Seismic Plastic) Stage 2,3 & 4 |
|
4 Cycles of stress variation from (-50%fy to 2εy) 4 Cycles of stress variation from (-50%fy to 5εy) Following the last cycle, the specimen shall be loaded
to failure in tension. |
Maximum % Elongation |
|
0.1 mm |
In Accordance
with ACI 318 – American Concrete Institute (ACI) Building Code 318,2008
Code is
basically a performance based code and categorizes splicing into two groups
Type 1 –
Joint require to achieve 1.25fy as minimum.
Type 2 –
Joint require to comply 1.25fy and meet specified tensile strength of rebar.
For Eg :For Fe500
Type 1 – Tensile strength is not expected to be less than 1.25fy =625N/mm^2
Type 2 - Tensile strength acceptance is at 700 N/mm^2