TxDOT – Standard and Criteria for Reinforcement Couplers

TxDOT – Standard and Criteria for Reinforcement Couplers

TEXAS DEPARTMENT OF TRANSPORTATION AUTHORIZATION ACCEPTANCE CRITERIA FOR MECHANICAL COUPLERS FOR REINFORCING STEEL under DMS-4510

 


TEXAS DOT

 

Type of Test Required

Why !

(Purpose of the test)

What is the Criteria ?

Static tensile strength test

Tensile strength of the Rebar joint

(Rebar to Coupler Splice) joint

 

>1.25Fy

 

Slip Test

 

Used to make sure that the plastic movement (slip) between the reinforcement bars with in the Mechanical Splice, when Loaded in tension

 

<=0.010 inch after applying 0.5fy loading

 

Fatigue Loading

Low Cycle Fatigue Test

 

The purpose of this test is to evaluate the performance of the splice reinforcement following significant inelastic stress reversal fatigue cycle which would stimulate a seismic event,

This includes a series of elastic stress reversal cycle followed by increasing inelastic stress reversal cycle out to 5 times the yield point strain of the reinforcement being tested.

 

In other words the purpose of fatigue testing of mechanical splices for steel reinforcement bars is to determine the fatigue strength of the mechanical splice.

 

The fatigue performance of a mechanically spliced bar will normally be lower than that of the un-spliced bar.

 

80,000 Cycles of alternating tension and compression load of 210 MPa.

 

 